Brand: Hager
Reference: MUN416A
4P magneto-thermal automatic switch with a nominal current of 16A. This curve C accessory has a voltage of 230/400V AC 50/60Hz and a cutting power of 6kA.
4P magneto-thermal automatic switch with a nominal current of 16A. This curve C accessory has a voltage of 230/400V AC 50/60Hz and a breaking power of 6kA.
Thus, the switch with a tightening torque of 2.8Nm has dimensions of 83x70x70mm. This device is characterized by maintaining the IP20 protection degree and an operating temperature of -25 to 60°C. Additionally, the MU series offers a variety of products with innovative and timeless designs focused on functionality. Likewise, the range offers switches with different technical characteristics.
Features:
Architecture
Number of protected poles
4
Number of poles
4 P
Type of poles
4 P
Curve
C
Functions
With neutral cut
No
Settings
Number of modules
4
Connectivity
Alignment of the upper terminals for modular devices
Aligned terminals
Alignment of the lower terminals for modular devices
Aligned bores
Main electrical characteristics
Assigned cutting power
6 kA
Assigned AC employment voltage
230 / 400 V
Type of supply voltage
AC
Assigned frequency
50/60 Hz
Tension
Assigned insulation voltage
500 V
Assigned impulse withstand voltage
4000 V
Electric current
Nominal assigned current
16 A
Service cutting power according to EN60898
6 kA
Min/max operating value of the thermal relay in AC.
1.13 / 1.45 In
Min/max threshold value magnetic relay in a.c.
5 / 10 In
Min/max operating threshold value of the thermal relay in DC
7 / 15 In
Value of the min/max operating level of the thermal relay in d.c.
1.13 / 1.45 In
1 pole cutting power 400V (EN60947-2)
3 kA
Assigned cutting power
6 kA
Last cut power in a.c. 400V (EN 60947-2)
10 kA
Last cut power in a.c. 415V (EN 60947-2)
10 kA
Current/temperature
Rated current at -25°C
20.4 A
Rated current at -20°C
20.1 A
Rated current at -15°C
19.7 A
Rated current at -10°C
19.3 A
Rated current at -5°C
18.9 A
Assigned current at 0°C
18.5 A
Assigned current at 5°C
18.1 A
Assigned current at 10°C
17.7 A
Assigned current at 15°C
17.3 A
Assigned current at 20º C
16.9 A
Assigned current at 25°C
16.5 A
Assigned current at 30° C
16 A
Assigned current at 35° C
15.5 A
Assigned current at 40° C
15 A
Assigned current at 45° C
14.4 A
Assigned current at 50° C
13.9 A
Assigned current at 55° C
13.3 A
Assigned current at 60° C
12.7 A
Assigned current at 65°C
12 A
Assigned current at 70° C
11.3 A
Current correction coefficient
Nominal current correction coefficient for 2 juxtaposed devices:
1
Nominal current correction coefficient for 3 juxtaposed devices:
0.95
Current correction coefficient for 4 and 5 juxtaposed devices:
0.9
Nominal current correction coefficient for 6 juxtaposed devices:
0.85
Magnetic trip correction coefficient at 100Hz
1.1
Magnetic trip correction coefficient at 200Hz
1.2
Magnetic trigger correction coefficient at 400Hz
1.5
Magnetic trip correction coefficient at 60Hz
1
Dimensions
Depth of installed product
70mm
Height of the installed product
83mm
Width of installed product
70mm
Frequency
Frequency
50 to 60 Hz
Power
Total power dissipated under conditions of nominal intensity
10.8 W
Power dissipated per pole
2.9 W
Endurance
Electrical endurance in number of cycles
4000
Mechanical endurance in number of maneuvers
20000
Installation, assembly
Top connection type for modular devices
Terminal with screws
Tightening torque
2.8 Nm
Lower connection type for modular devices
Double connection terminal
Connection
Sec. connection born. His p. and info. rigid cable
1 / 35 mm²
Section of connection of stud terminals with screw
1 / 25 mm²
Connection type
Cage terminal with screw
Rules
European WEEE Directive
affected
Security
IP protection index
IP20
Conditions of use
Operating temperature
-25…70 °C
Pollution degree / IEC60664/IEC60947-2
2
Energy limitation class I²t
3
Altitude
2000 m
Tropicalization/humidity/protection
All climates
Storage/transport temperature
-25…80 °C