Brand: Hager
Reference: MZ240N
Combined protection 2P+TT 6kA C-curve 40A
Combined protection 2P+TT 6kA C-curve 40A, Combined protection. against permanent and transient overvoltages 2P 6kA C40A 4M, MZ240N.
Technical characteristics
Architecture
Number of poles
2 P
Type of poles
2 P
Curve
C
Functions
With neutral cut
No
Settings
Number of modules
5
Main electrical characteristics
Assigned cutting power
6 kA
Assigned AC employment voltage
230 V
Type of supply voltage
AC
Assigned frequency
50/60 Hz
Tension
Assigned insulation voltage
500 V
Assigned impulse withstand voltage
4000 V
Electric current
Nominal assigned current
40 A
Service cutting power according to EN60898
6 kA
Min/max operating value of the thermal relay in AC.
1.13 / 1.45 In
Min/max threshold value magnetic relay in a.c.
5 / 10 In
Min/max operating threshold value of the thermal relay in DC
5 / 15 In
Value of the min/max operating level of the thermal relay in d.c.
1.13 / 1.45 In
1 pole cutting power 400V (EN60947-2)
3 kA
Assigned cutting power 230V 50 Hz
6 kA
Assigned cutting power
6 kA
Last cut power in a.c. 230V (EN 60947-2)
1 kA
Current/temperature
Assigned current at 20º C
43.2 A
Assigned current at 30° C
40 A
Assigned current at 35° C
38.4 A
Assigned current at 40° C
36.8 A
Assigned current at 45° C
35.2 A
Assigned current at 50° C
33.6 A
Assigned current at 55° C
32 A
Assigned current at 60° C
30.4 A
Assigned current at 70° C
27.2 A
Current correction coefficient
Nominal current correction coefficient for 2 juxtaposed devices:
1
Nominal current correction coefficient for 3 juxtaposed devices:
0.95
Current correction coefficient for 4 and 5 juxtaposed devices:
0.9
Nominal current correction coefficient for 6 juxtaposed devices:
0.85
Magnetic trip correction coefficient at 100Hz
1.1
Magnetic trip correction coefficient at 200Hz
1.2
Magnetic trip correction coefficient at 400Hz
1.5
Magnetic trip correction coefficient at 60Hz
1
Dimensions
Depth of installed product
70mm
Height of the installed product
86.5mm
Width of installed product
87.5mm
Frequency
Frequency
50 to 60 Hz
Power
Total power dissipated under conditions of nominal intensity
9.7 W
Endurance
Electrical endurance in number of cycles
10000
Mechanical endurance in number of maneuvers
10000
Connection
Sec. connection born. His p. and info. rigid cable
1 / 25 mm²
Section of connection of stud terminals with screw
1 / 16 mm²
Rules
European WEEE Directive
affected
Security
IP protection index
IP2X
atishalogenfreeexternallymaintained
No
Conditions of use
Operating temperature
-25…60 °C
Pollution degree / IEC60664/IEC60947-2
3
Energy limitation class I²t
3
Altitude
2000 m
Storage/transport temperature
-25…80 °C
See less