Brand: Hager
Reference: HNT251DR
Molded case circuit breaker,h3+ P250,4PN0-100%,250A,40kA relay TM reg.
Molded case automatic switch,h3+ P250,4PN0-100%,250A,40kA relay TM reg.
Technical characteristics
Architecture
Neutral position
Left
Number of protected poles
4
Number of poles
4 P
Box type
Built-in
Functions
Device equipped with protection function
Yes
Switch function
No
Head switch function
Yes
"Emergency stop" switch function
No
Safety switch function
No
Maintenance/service switch function
Yes
Trigger block
TM A/A
Integrated differential protection
No
With neutral cut
Yes
Controls and indicators
Integrated motorized control
No
Main electrical characteristics
Assigned AC employment voltage
220 / 690 V
Type of supply voltage
AC
Assigned frequency
50/60 Hz
Tension
Assigned insulation voltage
800 V
Assigned impulse withstand voltage
8 kV
Equipped with minimum voltage coil
No
Electric current
Nominal assigned current
250 A
Last cut power in a.c. 690V (EN 60947-2)
6 kA
Thermal regulation
0.63 / 0.8 / 1
Rated current at 10°C according to IEC 60947
310.2 A
Rated current at 15°C according to IEC 60947
303.3 A
Rated current at 20°C according to IEC 60947
296.3 A
Rated current at 25°C according to IEC 60947
289.1 A
Rated current at 30°C according to IEC 60947
281.7 A
Rated current at 35°C according to IEC 60947
274.1 A
Rated current at 40°C according to IEC 60947
266.3 A
Rated current at 45°C according to IEC 60947
258.3 A
Rated current at 50°C according to IEC 60947
250 A
Rated current at 55°C according to IEC 60947
241.4 A
Rated current at 60°C according to IEC 60947
232.5 A
Rated current at 65°C according to IEC 60947
223.3 A
Rated current at 70°C according to IEC 60947
213.7 A
ics947660
6 kA
Cutting power on 1 pole 230V (EN 60947-2)
6 kA
1 pole cutting power 400V (EN60947-2)
6 kA
1 pole cutting power. 415V (EN60947-2)
6 kA
Cutting power in 1 pole at 690 V (EN60947-2)
4.25 kA
Last cut power in a.c. 230V (EN 60947-2)
50 kA
Last cut power in a.c. 240V (EN 60947-2)
50 kA
Last cut power in a.c. 400V (EN 60947-2)
40 kA
Last cut power in a.c. 415V (EN 60947-2)
40 kA
Thermal regulation value
160 / 200 / 250 A
ics110138vaciec609472
50 kA
icu220vaciec609472
50 kA
icu380vaciec609472
40 kA
icu660vaciec609472
6 kA
Dimensions
Depth of installed product
97mm
Height of the installed product
165mm
Width of installed product
140mm
Frequency
Frequency
50 to 60 Hz
Power
Power dissipated per pole at 0.63 In
6.92 W
Power dissipated per pole at 0.8 In
10.82 W
Total dissipated power at 0.63 In
20.77 W
Total dissipated power at 0.8 In
32.45 W
Total power dissipated under conditions of nominal intensity
50.7 W
Power dissipated per pole
16.9 W
Shot
Quick shot (Short time)
No
Endurance
Electrical endurance in number of cycles
10000
Mechanical endurance in number of maneuvers
40000
Door, cover
Lockable by padlock
Yes
Installation, assembly
Tightening torque
12Nm
Optional mounting on DIN profile using adapter
Yes
Adapted to its mounting on a centered front panel
No
suitable for frontmounting
No
Adapted for floor mounting
Yes
Connection
Connection type
Terminals
Cable
Cable material
Cu / Al
Settings
Magnetic regulation current
1500 / 1750 / 2000 / 2250 / 2500 A
Magnetic regulation
6 / 7 / 8 / 9 / 10
Team
Number of normally closed auxiliary contacts
0
Number of normally open auxiliary contacts
0
Number of switched auxiliary contacts
0
Optional engine control
Yes
Accessory
Yes
Employment cases
Job category
A
Rules
Norm
IEC 60947-2
Security
atishalogenfreeexternallymaintained
No
Conditions of use
Pollution degree / IEC60664/IEC60947-2
3
Altitude
2000 m
Tropicalization/humidity/protection
95%RH 55°C sev Kn (IEC 68-2-30/52)
Temperature
Calibration temperature
50 °C