Brand: Hager
Reference: ND220A
N series magneto-thermal automatic switch, 2P, 20A, curve D, 10/15kA.
Neutral position
without neutral
Number of protected poles
2
Number of poles
2 P
Type of poles
2 P
Assembly
DIN rail
Curve
D
Functions
With neutral cut
No
Settings
Number of modules
2
Connectivity
Alignment of the upper terminals for modular devices
Aligned terminals
Alignment of the lower terminals for modular devices
Aligned bores
Main electrical characteristics
Assigned cutting power
10 kA
Assigned AC employment voltage
400 V
Type of supply voltage
AC
Tension
Assigned insulation voltage
500 V
Assigned impulse withstand voltage
6000 V
ueminimum
12 V
Electric current
Nominal assigned current
20 A
Service cutting power according to EN60898
7.5 kA
Min/max operating value of the thermal relay in AC.
1.13 / 1.45 In
Min/max threshold value magnetic relay in a.c.
10 / 14.4 In
Min/max operating threshold value of the thermal relay in DC
15 / 30 In
Value of the min/max operating level of the thermal relay in d.c.
1.13 / 1.45 In
Rated current at -10°C according to IEC 60947
26.75 A
Rated current at -15°C according to IEC 60947
27.24 A
Rated current at -20°C according to IEC 60947
27.72 A
Rated current at -25°C according to IEC 60947
28.19 A
Rated current at -5°C according to IEC 60947
26.26 A
Rated current at 0°C according to IEC 60947
25.75 A
Rated current at 10°C according to IEC 60947
24.71 A
Rated current at 15°C according to IEC 60947
24.17 A
Rated current at 20°C according to IEC 60947
23.62 A
Rated current at 25°C according to IEC 60947
23.06 A
Rated current at 30°C according to IEC 60947
22.48 A
Rated current at 35°C according to IEC 60947
21.88 A
Rated current at 40°C according to IEC 60947
21.28 A
Rated current at 45°C according to IEC 60947
20.65 A
Rated current at 5°C according to IEC 60947
25.24 A
Rated current at 50°C according to IEC 60947
20 A
Rated current at 55°C according to IEC 60947
19.33 A
Rated current at 60°C according to IEC 60947
18.64 A
Rated current at 65°C according to IEC 60947
17.92 A
Rated current at 70°C according to IEC 60947
17.17 A
Assigned cutting power 230V 50 Hz
10 kA
Assigned cutting power
10 kA
Last cut power in a.c. 230V (EN 60947-2)
30 kA
Last cut power in a.c. 240V (EN 60947-2)
30 kA
Last cut power in a.c. 400V (EN 60947-2)
15 kA
Last cut power in a.c. 415V (EN 60947-2)
15 kA
Assigned breaking capacity Icn at 240V AC according to IEC 60898-1
10 kA
Assigned breaking capacity Icn at 415V AC according to IEC 60898-1
10 kA
icu220vaciec609472
30 kA
icu380vaciec609472
15 kA
Current/temperature
Rated current at -25°C
25.08 A
Rated current at -20°C
24.66 A
Rated current at -15°C
24.24 A
Rated current at -10°C
23.8 A
Rated current at -5°C
23.36 A
Assigned current at 0°C
22.91 A
Assigned current at 5°C
22.45 A
Assigned current at 10°C
21.98 A
Assigned current at 25°C
20.51 A
Assigned current at 30° C
20 A
Assigned current at 35° C
19.47 A
Assigned current at 40° C
18.93 A
Assigned current at 45° C
18.37 A
Assigned current at 50° C
17.8 A
Assigned current at 55° C
17.2 A
Assigned current at 60° C
16.58 A
Assigned current at 65°C
15.94 A
Assigned current at 70° C
15.28 A
Current correction coefficient
Nominal current correction coefficient for 2 juxtaposed devices:
1
Nominal current correction coefficient for 3 juxtaposed devices:
0.95
Current correction coefficient for 4 and 5 juxtaposed devices:
0.9
Nominal current correction coefficient for 6 juxtaposed devices:
0.85
Magnetic trip correction coefficient at 100Hz
1.1
Magnetic trip correction coefficient at 200Hz
1.2
Magnetic trip correction coefficient at 400Hz
1.5
Magnetic trip correction coefficient at 60Hz
1.1
Dimensions
Depth of installed product
70mm
Height of the installed product
83mm
Width of installed product
35mm
Frequency
Frequency
50 to 60 Hz
Power
Maximum active power dissipated per pole according to product standard
4.5 W
Total power dissipated under conditions of nominal intensity
5.29 W
Power dissipated per pole
2.68 W
Endurance
Electrical endurance in number of cycles
4000
Mechanical endurance in number of maneuvers
20000
Installation, assembly
Top connection type for modular devices
Terminal with screws
Tightening torque
2.8 Nm
Top clip type for modular appliances
Not applicable
Type of DIN profile fixing clip for modular devices
Plastic
Lower connection type for modular devices
Double connection terminal
Superior disassembly for modular devices
Yes
Lower disassembly for modular appliances
Yes
Adapted for flush mounting
Yes
Connection
Maximum connection section of screw terminals with flexible cable
1 / 25 mm²
Rigid cable connection section in screw terminals at the top
1 / 35 mm²
Sec. connection top terminals in rigid cable
1 / 35 mm²
Screw terminal connection section on stud with flexible cable
1 / 25 mm²
position of the lower terminals
open
position of the upper terminals
open
Team
Accessory
Yes
withtransparentlabelholder
Yes
Rules
Norm
EN 60898-1, IEC 60947-2
European WEEE Directive
affected
Security
IP protection index
IP20
Conditions of use
Operating temperature
-25…70 °C
Pollution degree / IEC60664/IEC60947-2
2
Altitude
2000 m
Storage/transport temperature
-25…80 °C
Temperature
Calibration temperature
50 °C
See less