Brand: ABB
Reference: 2CSF204101R3630
Int.Dif.F204A-63/0.3 4P 63A A 300Ma 2Csf204101R3630
Reference 2CSF204101R3630 specifically is a residual current circuit breaker (RCCB).
Its features are:
Additional equipment possible, Frequency: 50/60 Hz, Protection class (IP): IP2X, Connectable solid conductor cross-section: 25mm², Connectable conductor cross-section: 25mm², Rated voltage surge withstand (Uimp): 4kV, Ambient temperature during operation: -25 - 55 °C, Pollution degree: 2, With locking device, Installation depth: 69mm, Width of division units: 4, Voltage type: AC
Technical
Standards:
IEC/EN 61008
UL 1053
Type of residual current:
Type A
Nominal voltage (Ur):
230/400 V
Nominal voltage operating voltage:
230 / 400 V AC
Rated insulation voltage (Ui):
500 V
Rated impulse withstand voltage (Uimp):
4 kV
Type of input voltage:
AC
Rated current (In):
63 A
Rated residual current:
300 mA
Rated conditional short-circuit current (Inc):
10 kA
Rated short-circuit breaking capacity in service (Ics):
1 kA
Type of leakage current:
A
Rated frequency (f):
50 … 60 Hz
Power Loss:
at Rated Operating Conditions per Pole 4.4 W
Power Supply Connection:
Arbitrary
Electrical Endurance:
10000 cycle
Number of Poles:
4
Operating Characteristics:
Instantaneous
Neutral Terminals Position:
Right
Mounting Type:
DIN-Rail
Options Provided:
None
Accessories Available:
Yes
Connection Capacity:
Busbar 10 mm²
Rigid 25 ... 25 mm²
Flexible 25 ... 25 mm²
Nominal cross section:
4 - Multi-Wired 0...25 mm²
1 - Solid-Core 25...25 mm²
Material Compliance
RoHS information:
9AKK106713A5602
RoHS status :
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS date:
20211115
REACH declaration:
9AKK108467A9482
Information REACH:
True - contains substances > 0.1 mass percentage
REACH date:
20240429
Conflict Minerals Notification Template (CMRT):
9AKK108468A3363
Environment
Ambient temperature:
-25...55 °C
Ambient temperature:
Operating -25...55 °C
Protection degree:
IP2X
Pollution degree:
2
Vibration resistance according to IEC 60068-2-6:
20 Cycles with Load 0.8 In: 1g or 1mm 50 … 150 … 5 Hz
Shock resistance according to IEC 60068-2-27:
25g 2 shocks 13 ms
Environmental information:
Refer to RoHS
Technical UL/CSA
UL/CSA maximum operating voltage:
480Y / 277 V AC
Short circuit current rating (SCCR):
300 mA
Dimensions
Width in number of modular spaces:
4
Product width:
0.070 m
Product height:
0.085 m
Product length:
0.069 m
Product weight: product:
0.360 kg
Built-in depth (t2):
69 mm
Dimensions:
9AKK106354A0759
Classification
Packaging Level 1 Units:
box 1 piece
Packaging Level 1 Weight:
0.415 kg
E-number (Finland):
3259464
E-number (Sweden):
2160131