Brand: ABB
Reference: 2CDS252001R0324
S202-C32 Circuit Breaker - 2P - C - 32 A 2Cds252001R0324
The reference 2CDS252001R0324 specifically, is a magneto-thermal switch.
Its characteristics are:
Assigned breaking capacity Icu according to EN 60947-2 at 230 V: 20kA, Solid connectable conductor section: 0.75 - 35 mm², Connectable conductor section: 0.75 - 25 mm², Ambient temperature during operation: -25 - 55 °C, Additional equipment possible, Number of poles (total): 2, Rated breaking capacity Icn according to EN 60898 at 230 V: 6kA, Rated surge voltage resistance (Uimp): 4kV, Number of protected poles: 2, Rated breaking capacity Icu according to EN 60947-2 at 400 V: 20kA, Rated breaking capacity Icn according to EN 60898 at 400 V: 6kA, Frequency: 50Hz.
Technical
Rules:
IEC/EN 60898-1
IEC/EN 60947-2
UL 1077
Stumble feature:
C
Nominal operating voltage:
acc. to IEC 60898-1 400 V AC
acc. to IEC 60898-1 400 V
acc. to IEC 60947-2 440 V AC
Operating voltage:
Maximum (Incl. Tolerance) 125 V DC
Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC
Minimum 12 V DC
Nominal insulation voltage (Ui):
acc. to IEC/EN 60664-1 440 V
Nominal voltage supported by impulses (Uimp):
4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Dielectric test voltage:
50/60 Hz, 1 min: 2 kV
Input voltage type:
AC/DC
Nominal current (In):
32 A
Nominal short circuit capacity:
(AC) 6 kA
(DC) 6 kA
(400 V AC) 6 kA
(400 V) 6 kA
Nominal short circuit breaking capacity (Icu):
(125 V DC) 10 kA
(230 V AC) 20 kA
(400 V AC) 10 kA
(440 V AC) 10 kA
(48 V DC) 20 kA
(230 V) 20 kA
(400 V) 10 kA
Rated conditional short circuit current (Inc):
(230 V) 20 kA
(400 V) 20 kA
Nominal short-circuit breaking capacity in service (Ics):
(230 V AC) 15 kA
(400 V AC) 7.5 kA
(440 V AC) 7.5 kA
Frequency (f):
50 Hz
Nominal frequency (f):
50 / 60 Hz
Power loss:
7.4 W
at Rated Operating Conditions per Pole 3.7 W
Power supply connection:
Arbitrary
Contact position indication:
Red ON / Green OFF
Power limitation class:
3
Electrical resistance:
10000 AC cycle
Mechanical resistance:
20000 cycle
Number of protected posts:
2
Number of poles:
2
Surge category:
III
Tightening torque:
2.8 N·m
Mounting type:
DIN-Rail
Screw terminal type:
Failsafe Bi-directional Cylinder-lift Terminal
Actuator marking:
I/O
Actuator material:
Insulation Group II, Black, Sealable
Housing material:
Insulation Group II, RAL 7035
Mounting on contactors:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting position:
any
Recommended screwdriver:
Pozidriv 2
Available accessories:
Yes
Connection capacity:
Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
Installation size:
acc. to DIN 43880 1
Cable stripping length:
12.5mm
Terminal type:
Screw Terminals
Material Compliance
RoHS information:
2CDK403001D0607
RoHS status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS date:
0335
REACH declaration:
9AKK108468A9644
REACH information:
True - contains substances > 0.1 mass percentage
REACH date:
20231212
Conflict Minerals Reporting Template (CMRT):
9AKK108468A3363
SCIP:
e6800e55-46b1-49a3-881b-0f66d0e903ad Germany (DE)
Environment
Ambient temperature:
Operation -25 ... +55 °C
Storage -40 ... +70 °C
Reference ambient air temperature:
30 °C
Degree of protection:
IP20
IP40
Enclosure with Cover IP40
Degree of contamination:
3
Environmental conditions:
28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Vibration resistance according to IEC 60068-2-6:
20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz
Shock resistance according to IEC 60068-2-27:
25g 2 shocks 13 ms
Technical UL/CSA
UL/CSA maximum operating voltage:
110V DC
480Y/277V AC
Interrupting capacity according to UL1077:
(277 V AC) 6 kA
(480Y / 277 V AC) 6 kA
(240 V) 10 kA
UL/CSA connection capacity:
Busbar 18-8 AWG
Conductor 18-4 AWG
UL/CSA tightening torque:
18 in·lb
Dimensions
Width in number of modular spaces:
2
Product width:
35mm
Height of the product:
88mm
Product length:
69mm
Product weight:
0.25 kg
Pole net weight:
0.125 kg
Built-in depth (t2):
69mm
Dimensions diagram:
2CDC022007F0010
Classification
Packaging Level 1 Units:
carton 5 piece
Packaging Level 1 Weight:
1.3 kg
E number (Finland):
3210532
E number (Sweden):
2100566
Certificates and Declarations (Document Number)
Certification agency:
EN
IEC
UL
Declaration of conformity - CE:
2CDK403001D0607
Declaration of conformity - UKCA:
9AKK108467A5053
I²t Feature:
9AKK107992A5102
Installation
Instructions and manuals:
2CDS207104P0002
Popular Downloads
Technical sheet, technical information:
9AKK107991A8329
I²t Feature:
9AKK107992A5102
Classifications
ETIM 8:
EC000042 - Miniature circuit breaker (MCB)
ETIM 9:
EC000042 - Miniature circuit breaker (MCB)
WEEE category:
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B:
Business To Business
CN8:
8536 20 10
UNSPSC:
39121603
Electronic class:
V11.0: 27141901
IDEA Granular Category Code (IGCC):
4897 >> Miniature circuit breakers
Object classification code:
F