Brand: CIRCUTOR
Reference: P10154.
Wgc-80 Toroidal Transformer Diameter 80Mm. In this new range, a series of improvements are presented, especially thinking about the installation of equipment in distribution boards.
WGC-80 toroidal transformer, diameter 80mm. In this new range, a series of improvements are presented, especially thinking about the installation of equipment in distribution boards. In addition to the usual fixings for installation, the possibility of doing so on a DIN rail using an accessory is added, making installation easier.
The WGC series differential transformer has better immunity against transient current spikes that usually cause differential protection trips. The WGC series differential transformer are designed to work with the WGC series relays. The sensitivity (trigger current) of the transformer-relay assembly is set by the associated relay.
SPECIFICATIONS
ALTERNATION POWER SUPPLY (INSULATION)
Impulse test (kV)
3 kV
MECHANICAL CHARACTERISTICS
Size (mm) width x height x depth
124.5 x 130 x 50 (mm)
Envelope
Self-extinguishing polycarbonate UL 94 V0
Fixation
DIN rail with accessory (see code)
Connection type
Screwable terminal (Pz screw type)
Net Weight (kg)
0.288
ENVIRONMENTAL CHARACTERISTICS
Degree of protection
IP 20 (Terminals) IEC 60529
Relative humidity (non-condensing)
5 ... 95 %
Working temperature
-20 ... + 70 ºC
CURRENT MEASUREMENT CIRCUIT
Dynamic intensity (Idyn)
2.5 Ith
Permanent thermal intensity (Icth)
60 A
Short circuit thermal intensity (Ith)
1.8 kA / 1s
Transformation ratio
30 / 0.06 A
Maximum service voltage (Um)
720 V
RULES
Electrical safety, Max altitude. (m)
2000
Electrical safety, Installation category
CAT III
Rules
IEC 60664-1, IEC 60664-3, IEC 60044-1
PRECISION OF MEASUREMENTS
Precision
10 … 15 %